1 Installation of Low-voltage Circuit Breaker,Low-voltage Contactor and Motor Starter
1.0.1 This chapter is applicable to the installation of low-voltage circuit breaker,low-voltage contactor and motor starter at rated voltage of 500V and below.Low-voltage circuit breaker,low-voltage contactor and motor starter shall be checked as per 100% of low-voltage circuit breaker on incoming line,and other lowvoltage circuit breakers shall be spot checked as per 10% quantity.Low-voltage contactors and motor starters shall be spot checked as per 10% quantity.
1.0.2 Table 1.0.2 refers to the installation and checkout of low-voltage circuit breaker,low-voltage contactor and motor starter.
Table 1.0.2 Installation of low-voltage circuit breaker,low-voltage contactor and motor starter